Questions to Ask Your HVAC Contractor
By Danish Javaid, founder & editor · Published · Updated

Ask every contractor the same five things: what are my heating and cooling loads and can I see the report, why these exact models, what did you measure about my ducts, what is and is not in the price, and how will you prove it works at startup. A contractor who answers with documents and numbers is sizing from design; one who answers "we always put in four tons for a house this size" is not, and a U.S. Department of Energy guide for homeowners names exactly that rule-of-thumb habit as a cause of oversized systems.
On the phone, before anyone drives out
- Do you calculate the load with Manual J, and will I get the report? A real report lists the inputs (areas, insulation, windows, leakage, design weather) and gives heating plus cooling split into sensible and latent. Run your own estimate first with the Manual J calculator so you know the neighborhood, and see what Manual J is if the terms are new.
- Will you look at my ducts? New equipment on undersized or leaky ducts underperforms whatever its rating. A good answer mentions measuring airflow and static pressure and checking the return paths; see the static pressure guide.
- Which licenses and permits apply here, and who pulls the permit? Rules differ by state and city, so verify the license and insurance yourself through the local licensing authority rather than taking the card on the truck. A permit adds a third-party inspection; a suggestion to skip it is a reason to keep looking.
At the site visit
| Ask | A useful answer contains | Ask again if you hear |
|---|---|---|
| What are the loads? | Heating, sensible, latent and total cooling, with the design conditions | A square-foot or old-unit rule |
| Why these models? | Capacity at your design conditions for the exact matched indoor and outdoor units | Nominal tonnage or an "up to" efficiency claim |
| What happens on the coldest design day? (heat pumps) | Output at that temperature, backup heat, control sequence | No low-temperature data |
| Can the ducts carry the airflow? | Measurements and a priced repair scope if needed | No return-path or pressure check |
| What efficiency, and why? | Exact SEER2, EER2 and HSPF2 for the matched system, with assumptions behind any savings | A top tier with no reasoning |
What a sizing answer looks like with numbers
You ask what size your 1,800 ft² house needs. Contractor A says four tons because that is what goes in houses this size. Contractor B shows a report: design cooling 31,200 BTU/h (25,200 sensible and 6,000 latent) and proposes a 3-ton model whose published capacity at your design conditions is 33,500 BTU/h total with 25,800 sensible. All numbers here are assumed.
| Check | Contractor A | Contractor B |
|---|---|---|
| Source of size | Habit | Calculated report |
| Capacity | 48,000 BTU/h (4 × 12,000) | 33,500 BTU/h at design conditions |
| Capacity ÷ load | 48,000 ÷ 31,200 = 154% | 33,500 ÷ 31,200 = 107% |
| Sensible covered | Not shown | 25,800 vs 25,200, yes |
| Latent covered | Not shown | 33,500 − 25,800 = 7,700 vs 6,000, yes |
The point is checkability, not that B is automatically right. Designers usually want delivered total cooling in roughly the 95 to 115% range of the calculated load, with exact limits depending on the Manual S edition and equipment type, and furnace output compared with the heating load in a wider band; see what size furnace for the conversion from input to output. What a 154% system does in your house is described in the oversizing symptoms guide.
When the written quote arrives
- What exactly is included: models, line sets, electrical, duct changes, thermostat, drain, haul-away, permit fees?
- What can trigger a change order, and do I approve the price before the work?
- What are the parts and labor warranties, who registers the equipment and by what date, and what voids it?
- If the quote uses a newer refrigerant such as R-454B or R-32, may the old coil or line set be reused under the manufacturer's instructions?
- If a federal heat pump tax credit is mentioned for a 2026 installation: which program? The 25C credit does not apply to property placed in service after December 31, 2025. State and utility rebates need written confirmation of eligibility before they count.
- How will you verify startup? Expect airflow and static pressure readings, charge by the manufacturer's procedure, drain and controls checks, combustion safety for fuel-fired equipment, and a written record.
Warranty terms vary by manufacturer and registration, and a permit inspection does not certify performance, so get the actual terms and the commissioning record in writing. Once you have several quotes, use the quote verification guide to normalize scope and the Manual J report guide to read the load documents themselves. If two reports disagree, ask each contractor to walk through the differing inputs (windows, leakage, ventilation, design weather) rather than averaging them.
Sources: DOE Building America, HVAC: A Guide for Contractors to Share with Homeowners (2011; load calculation instead of rules of thumb); ACCA Manual J and Manual S; IRS: 25C not allowed after Dec. 31, 2025.
Calculation guidance is reviewed against our published methodology. To report an error or request a correction, use the contact page.
Written and maintained by Danish Javaid, founder & editor. About this site.
Revision history
- : Restructured the questions by stage with a good-answer table, and added a DOE citation plus the 25C credit expiry.
- : Added an example contrasting a rule-of-thumb sizing answer with a calculated one.