Psychrometric Cooling Load Calculator
Compare sensible and latent approximations with moist-air enthalpy using temperatures and humidity ratios.
Accepted range: 0 to 1000000.
Accepted range: 32 to 120.
Accepted range: 32 to 120.
Accepted range: 0 to 300.
Accepted range: 0 to 300.
Formula used
Qs = 1.08 * CFM * (Tin - Tout); Ql = 0.68 * CFM * (Win - Wout); h = 0.240 * T + (W / 7000) * (1061 + 0.444 * T); Qt = 4.5 * CFM * (hin - hout)
Cooling/dehumidification only: leaving temperature and humidity ratio cannot exceed entering values. Saturation is checked using ASHRAE Fundamentals water-vapor pressure at 101.325 kPa. Temperatures are limited to 32-120F. Fixed sensible/latent constants are approximations; their sum differs slightly from the enthalpy method.
Tracing the coil on a chart
Plot the entering and leaving air and the process line splits into two legs: a horizontal run that removes temperature only, then a drop that removes moisture. With the default 1,000 CFM case, 80°F air falling to 55°F accounts for 27,000 BTU/h of sensible load, and the 30-grain moisture drop adds 20,400 BTU/h of latent load, so only about 57% of the work is sensible. Leaving air that sits near the saturation curve is why a coil colder than the entering dew point wrings water out of the air. Switch the example to see how a dry-air case collapses to a single horizontal line.
The sensible, latent and enthalpy equations
Every air-side load splits into two parts. Sensible load comes from the dry-bulb temperature change; latent load comes from the moisture change. Adding them gives an approximate total for the coil. The calculator also computes the total from the moist-air enthalpy difference, which is the more fundamental route, so you can see how close the shortcut constants are. If you only know a supply airflow target, the CFM / airflow calculator works the reverse direction.
Temperatures in °F, dry-bulb. 1.08 is the standard-air sensible constant.
W in grains of moisture per lb of dry air. 0.68 is the standard-air latent constant.
Btu per lb of dry air, T in °F, W in grains/lb (ASHRAE Fundamentals form).
4.5 = 60 min/h × 0.075 lb/ft³. Do not add the two total estimates together.
These are the same air-side relationships used in a Manual J load calculation and described in the HVAC load calculation formula guide.
Worked example with default inputs
| Input | Example value |
|---|---|
| Standard-density airflow | 1,000 CFM |
| Entering dry-bulb | 80 F |
| Leaving dry-bulb | 55 F |
| Entering humidity ratio | 90 grains/lb dry air |
| Leaving humidity ratio | 60 grains/lb dry air |
Sensible: 1.08 × 1,000 × (80 − 55) = 27,000 BTU/h. Latent: 0.68 × 1,000 × (90 − 60) = 20,400 BTU/h. Sum of the approximations: 47,400 BTU/h, with an approximate SHR of 27,000 ÷ 47,400 ≈ 0.57. By enthalpy: h in ≈ 33.30 and h out ≈ 22.50 Btu/lb, so Qt = 4.5 × 1,000 × 10.79 ≈ 48,575.314 BTU/h (about 4.05 tons), slightly above the shortcut sum because the enthalpy form includes the vapor's heat content as temperature changes.
Example results at 1,000 CFM
| Scenario | Dry-bulb ΔT | Grains Δ | Sensible BTU/h | Latent BTU/h | SHR |
|---|---|---|---|---|---|
| Dry climate cooling | 25 °F | 10 gr | 27,000 | 6,800 | 0.80 |
| Standard comfort coil | 25 °F | 30 gr | 27,000 | 20,400 | 0.57 |
| Humid climate cooling | 20 °F | 40 gr | 21,600 | 27,200 | 0.44 |
| Sensible-only (dry coil) | 20 °F | 0 gr | 21,600 | 0 | 1.00 |
| Dehumidification-focused | 8 °F | 45 gr | 8,640 | 30,600 | 0.22 |
Values use the approximate constants and are illustrative. Notice how a large grains difference pulls SHR down even when the temperature drop is modest; that is a coil doing mostly dehumidification work. The last row is a dehumidification-focused case such as a unit that reheats or removes moisture without much cooling, not a typical comfort coil.
Common psychrometric mistakes
- Mixing up dry-bulb and wet-bulb temperatures — the sensible formula uses dry-bulb only; moisture is handled separately through grains.
- Entering relative humidity directly. RH must first be converted to a humidity ratio in grains/lb at the actual temperature, because the same RH holds far more moisture at higher temperatures.
- Forgetting the 1.08 and 0.68 constants are tied to standard-density air — at high elevation the air is less dense and both shrink.
- Adding the shortcut total and the enthalpy total together. They are two estimates of the same load, not two loads.
- Entering supersaturated leaving air — a humidity ratio above the saturation value at the leaving temperature is not a valid state.
- Sizing equipment on total load alone and ignoring SHR — a coil with the wrong SHR leaves the space cold and clammy or hot and dry.
- Using entering-air conditions as the leaving state. The temperature and grain differences must be taken across the coil, not at a single point.
- Assuming the coil dehumidifies. If the leaving grains equal the entering grains, latent load is zero and the coil is running dry.
Reading the psychrometric chart behind the numbers
The two air-side equations on this page are shortcuts for moving between points on a psychrometric chart. The chart, standardized in the ASHRAE Handbook - Fundamentals, plots every possible moist-air state on one diagram: dry-bulb temperature runs along the horizontal axis, the humidity ratio (grains of moisture per pound of dry air) runs up the vertical axis, and the curving lines crossing the field are constant wet-bulb temperature, constant relative humidity and constant enthalpy. Any two of those properties fix a single point, and once you have the point you can read off the others, including the dew point, where the air would begin condensing if cooled further.
A cooling coil traces a line from the entering air state to the leaving air state. When that line moves straight left at constant humidity ratio, the coil is doing pure sensible work and the latent load is zero. When the line also drops downward toward lower grains, the coil surface has fallen below the entering air's dew point, moisture is condensing and you pick up latent load. The slope of that process line is what the sensible heat ratio describes. The 1.08 constant captures the horizontal (temperature) move and 0.68 captures the vertical (moisture) move, both scaled by standard air density near sea level. At higher elevation the air thins out, so both constants shrink and the chart you would use changes with them.
Enthalpy ties the two halves together. It is the total heat content of the air in Btu per pound of dry air, sensible and latent combined. Reading the enthalpy difference across the coil and multiplying by the mass flow is a third route to the same total, and it is a useful check on the separate sensible and latent figures, since rounding the grains can quietly distort the split.
Why SHR drives equipment selection, not just total tonnage
Most people size cooling equipment on total load alone: find the BTU/h, divide by 12,000 BTU/h per ton and pick a unit. That ignores one of the most important air-side properties for comfort, the sensible heat ratio. A space whose load has an SHR of 0.75 needs a coil that removes one unit of moisture heat for every three units of temperature heat. If the selected equipment delivers an SHR of 0.90, it can satisfy the thermostat on temperature before it has removed enough water, short-cycle and leave the room cool and clammy at a high relative humidity, well outside most comfort targets. ASHRAE guidance generally keeps indoor humidity under roughly 60 to 65% RH, with the exact comfort zone depending on temperature, clothing and activity.
AHRI publishes rated capacities for matched indoor and outdoor units, and those ratings list sensible and total capacity separately at standard conditions, which lets you back out the equipment SHR. The practical workflow is to establish the design loads first (a full ACCA Manual J gives sensible and latent totals), then use the leaving air state from this calculator to confirm a candidate coil can reach the supply moisture you need. Efficiency metrics such as SEER2, EER2 and HSPF2 tell you how cheaply the box runs; they say nothing about whether it dehumidifies, so SHR has to be checked independently, and Manual S selection works from sensible and latent capacity at design conditions.
- High-SHR loads: dry climates, tight envelopes and low occupancy — standard single-stage equipment sized close to the sensible load can work.
- Mid-SHR loads: mixed-humid climates and typical homes — variable-speed or two-stage equipment, with longer lower-airflow cycles, can strip more moisture.
- Low-SHR loads: humid climates, high occupancy, pools and kitchens — may need a dedicated dehumidifier or a dedicated outdoor-air system alongside the cooling coil.
Airflow is a lever that shifts SHR on a given coil. A common design figure is around 400 CFM per ton for good sensible capacity; slower airflow over the same coil lowers the coil surface temperature and increases moisture removal, within the manufacturer's limits (too little air risks coil freezing). You can test that trade-off directly by changing the airflow input here, or work the airflow target itself with the CFM calculator. For the whole-house load that feeds these numbers, start from the Manual J calculator, check capacity at design conditions with the Manual S calculator, and see the HVAC load calculation formula guide for how the pieces roll up into a single tonnage.
Scope and source of the air-property equations
This psychrometric calculator evaluates cooling and dehumidification between entered air states at standard density; it excludes heating, humidification, altitude adjustment, and deriving humidity ratio from relative humidity.
ASHRAE Fundamentals describes humidity ratio, saturation, and moist-air enthalpy. The tool checks saturation at 101.325 kPa and reports both constant-coefficient load estimates and a separate enthalpy-difference total.
Recording an entering and leaving air test
Take the temperature and moisture readings for each air state at the same location and operating condition, and let the system stabilize before recording them. Enter dry-bulb temperature in F and humidity ratio in grains per pound of dry air. Relative humidity requires temperature and pressure to convert to humidity ratio; this calculator accepts the resulting ratio rather than doing that conversion.
Use an airflow measured or established for the same test, rather than assuming the fan's nominal tonnage setting proves actual flow. At the defaults, entering enthalpy is 33.2981 and leaving enthalpy is 22.5036 BTU/lb dry air. Their difference is about 10.7945; multiplying by 4.5 times 1,000 gives 48,575.314 BTU/h. The shortcut total is 47,400, so report which method you used instead of adding the two results. The airflow relationships explain the sensible-only equation, and the water-removal balance expresses a moisture stream in pounds per hour and pints per day.
Psychrometric calculator FAQ
Quick answers to common HVAC sizing questions.
Next steps
- Dehumidifier Moisture Load Calculator Size a dehumidifier for the moisture you just found in the air.
- Home Ventilation Calculator | ASHRAE 62.2 Baseline Estimate outdoor air volume and the humidity it carries in.
- HVAC Tonnage Calculator Compare the nominal tons you plan to buy with the humidity load behind latent capacity.
Built and maintained by Danish Javaid · How this calculator works: Methodology · Editorial policy