Calculate HVAC Load

Manual J Calculator (Simplified)

Room-by-room cooling and heating load calculator with sensible, latent, and total cooling, heating BTU, and per-room CFM. Add as many rooms as your project needs.

Project

Climate zone applies to all rooms.

Whole-house totals — Zone 4 — Mixed (DC, Nashville, Seattle)

Total cooling load
35,336BTU/hr
Recommended size
3tons
Required airflow
1,308CFM
Sensible cooling
28,280BTU/hr
Latent cooling
7,056BTU/hr
Total heating load
33,390BTU/hr
RoomSensibleLatentTotal coolHeatCFM
Living room13,5963,31916,91514,884629
Kitchen6,3381,6688,0067,875293
Master bedroom8,3462,06910,41510,631386

Simplified Manual J — applies climate-zone rates with envelope (insulation, exterior walls, windows), sun, ceiling, and occupant adjustments. For permitting or rebate documentation, run a full ACCA-approved Manual J via certified software.

Visualization

Block load vs room-by-room

The diagram below shows the two Manual J methods side by side. Block load gives one whole-house number. Room-by-room gives every room its own load and airflow — required for zoned systems, ductless, and any project where Manual D ductwork follows.

32,000 BTU/hrone zone · one airflow

Block load — fast and approximate

  • One whole-house BTU number
  • Best for single-zone systems < 2,000 sq ft
  • Cannot identify under-served rooms
  • Cannot drive Manual D duct sizing

Formula

What Manual J calculates per room

Sensible cooling load
Q_s = (Sqft × Cooling rate × Adjusters) + Window solar + Occupant sensible + Appliance load
Latent cooling load
Q_l = Sensible × latent ratio + Occupant latent + Infiltration latent

Latent ratio: 30% in humid zones (1–3), 20% otherwise.

Heating load
Q_h = Σ (U × A × ΔT) + (1.08 × Infiltration CFM × ΔT)
Required CFM (per room)
CFM = Sensible BTU/hr ÷ (1.08 × 20°F)

20°F is the typical supply air ΔT in residential cooling.

Reference

The 8 building factors Manual J analyzes

FactorWhy it mattersTypical input source
Envelope assembliesConduction path for heatConstruction docs or visual inspection
Insulation R-valueResists heat flowSpec sheet or audit
Windows (U + SHGC)Largest single variableNFRC label or product cut sheet
InfiltrationAir leakage drives heating + latent coolingBlower door test or estimated ACH
Internal gainsPeople, lights, appliancesOccupancy schedule + appliance list
Duct lossesUnconditioned-space ducts add 15–25% to loadDuct location + R-value
Outdoor design tempSets ΔT magnitudeASHRAE handbook by ZIP
Indoor design tempCooling: 75°F, heating: 70°F (typical)Project specification

Workflow

From Manual J to a finished install

  • Manual J — calculate room-by-room cooling and heating loads (this tool)
  • Manual S — select equipment that matches the load curve at your design conditions
  • Manual D — design supply and return ducts using per-room CFM
  • Manual T — select supply air registers and grilles by velocity and throw
  • Manual RS — verify design comfort criteria (humidity, draft, stratification)

ACCA design sequence. Each step depends on the prior; skipping any one introduces sizing or comfort errors that show up after install.

Manual J FAQ

Quick answers to common HVAC sizing questions.