Calculate HVAC Load

Complete HVAC System Sizing

End-to-end sizing in one screen: cooling load, heating load, equipment tonnage, required CFM, and recommended duct size — all from your home's basic envelope inputs.

Inputs
sq ft
ft
people
Results
Cooling load
63,075BTU/hr
Heating load
86,625BTU/hr
Recommended size
5.5tons
Required airflow
2,200CFM
Round duct
16"
Duct velocity
1,576FPM
Exact tonnage
5.26tons
Recommended BTU
66,000BTU/hr

Visualization

The full sizing chain in one view

From cooling load to recommended duct size — the four conversions residential HVAC sizing relies on. Adjust the BTU/hr value to watch tonnage, CFM, and duct size update live.

Live conversion

BTU → Tons → CFM → Duct size
BTU/hr
    Cooling load36,000BTU/hr
    ÷ 12,000
    Equipment size3.00tons (round to 3)
    × 400 CFM/ton
    Required airflow1,200CFM
    duct table
    Round duct14"diameter

Standard residential rules: 12,000 BTU/hr per ton, 400 CFM per ton, and a duct sized for ≤ 900 FPM at 0.08 in. w.g. friction. High-efficiency variable-speed systems use 350 CFM/ton.

Formula

The four conversions

1 — Load to tonnage
Tons = BTU/hr ÷ 12,000

Round to nearest 0.5 ton.

2 — Tonnage to airflow
CFM = Tons × 400

Use 350 for high-efficiency variable-speed.

3 — Airflow to duct size
d = √(4 × CFM ÷ (π × velocity)) × 12

d in inches, target velocity 700 FPM for trunks.

4 — Heating capacity
Furnace BTU/hr = Heating load × 1.10–1.15

10–15% safety margin above design heating load.

Reference

Whole-house sizing by climate and area

HomeClimate zoneAC tonsFurnace BTUTrunk duct
1,200 sq ftZ2 (hot)2.540,0009″
1,500 sq ftZ4 (mixed)2.560,00010″
1,800 sq ftZ3 (warm)350,00012″
2,200 sq ftZ5 (cool)380,00012″
2,800 sq ftZ2 (hot)4.570,00014″
3,200 sq ftZ6 (cold)3.5100,00012″
3,800 sq ftZ3 (warm)590,00016″

Workflow

The right order to size a system

  • 1. Cooling load (BTU/hr) — drives compressor tonnage
  • 2. Heating load (BTU/hr) — drives furnace size or heat-pump capacity at design temp
  • 3. Tonnage rounding — pick the nearest 0.5 ton above the cooling load
  • 4. CFM at 400/ton — sets blower speed and duct sizing target
  • 5. Trunk and branch duct sizing — based on per-room CFM and target friction
  • 6. Manual S equipment selection — match the model number to performance specs
  • 7. Manual D duct layout — finalize trunk routes, branches, and registers

Background

Why the J → S → D sequence exists

Whole-system sizing is not a single calculation — it is a chain of three dependent decisions that the Air Conditioning Contractors of America (ACCA) codified into separate manuals precisely because each step relies on the output of the one before it. The sequence runs Manual J, then Manual S, then Manual D, and skipping or reordering it is the root cause of most uncomfortable, noisy, or short-cycling installations.

Manual J answers the first question: how much heat does this specific house gain in summer and lose in winter at the local 1% and 99% design conditions? It produces two numbers in BTU/hr — a sensible plus latent cooling load and a heating load — built up from the envelope you describe through U-values, R-values, glazing area, infiltration, orientation, and internal gains. Nothing downstream is trustworthy if this number is wrong, which is why a careful room-by-room Manual J is the foundation rather than a square-footage rule of thumb.

Manual S takes that load and selects real, AHRI-matched equipment. A load of, say, 28,000 BTU/hr of cooling does not mean "buy a 2.5-ton unit" in the abstract — it means find an indoor-coil-plus-outdoor-unit combination whose published AHRI capacity at your design temperature, and at your target airflow, lands within ACCA's allowed window above the load (generally no more than 115% of the cooling load, and ideally close to it). Manual D then designs the duct system that delivers the airflow that the selected equipment requires. Each manual literally cannot start until the previous one finishes.

In practice

Balancing heating against cooling capacity

The trickiest part of system sizing is that one box rarely satisfies both loads cleanly. Compressor tonnage is governed by the cooling load, because an oversized cooling coil cannot dehumidify — it satisfies the thermostat in a few minutes and shuts off before latent moisture is removed. Heating capacity, however, is a separate spec: for a gas furnace it is the input rating and AFUE; for a heat pump it is the integrated capacity at the design outdoor temperature, declining as it gets colder.

In most IECC climate zones the heating load exceeds the cooling load, sometimes by a factor of two. That gap is why pairing decisions matter. A furnace can simply be specified at a higher BTU/hr input while the matched AC coil is sized to the cooling load. A heat pump is harder: its capacity falls exactly when heating demand rises, so the balance point — the outdoor temperature where heat-pump output equals the building's heat loss — drives whether you need auxiliary electric strips, a larger variable-speed unit, or a dual-fuel configuration. Efficiency metrics enter here too: SEER2 and EER2 describe cooling performance, while HSPF2 describes seasonal heating performance, and the federal minimums published by the DOE and the ENERGY STAR tiers from the EPA set the floor for what is worth buying.

  • Cooling sizing target: nearest 0.5 ton at or just above the Manual J cooling load (1 ton = 12,000 BTU/hr)
  • Heating sizing target: design heating load plus a 10–15% margin for furnaces; balance-point analysis for heat pumps
  • Airflow link: roughly 400 CFM per ton (350 CFM/ton for high-efficiency variable-speed coils)
  • Equipment check: confirm the combination appears in the AHRI Directory of Certified Product Performance

Standards

From airflow to duct geometry, and back to the load

Once Manual S fixes the equipment and its rated airflow, Manual D sizes the trunks and branches to move that air at an acceptable friction rate and velocity. This is where the chain can quietly break: a perfectly sized 3-ton system feeding undersized ducts behaves like an oversized one, because high external static pressure chokes airflow, starves the coil, raises noise, and shortens blower life. The duct design must hit the per-room CFM that the Manual J room loads called for — closing the loop back to the very first step. Our duct size calculator applies the same velocity and friction targets that Manual D uses, and the Manual J, S, and D walkthrough shows how the three fit together on a real house.

The figures embodied in these methods trace back to ACCA's residential procedures and the ASHRAE Handbook of Fundamentals, which supplies the heat-transfer coefficients, design weather data, and ventilation guidance (ASHRAE 62.2 for dwelling-unit ventilation) that Manual J draws on. None of that is exotic math — it is bookkeeping of heat flows — but the discipline is in respecting the order. Get the load right, choose AHRI-matched equipment that fits it without overshooting, then design ducts to deliver the airflow that equipment needs. Reverse any two of those steps and the comfort, humidity control, and efficiency you paid for all degrade together.

For single-zone, single-family homes a whole-house block load is an appropriate starting point, and the estimate above will land close to a formal result. For zoned systems, ductless mini-splits, additions, or anything bound for a permit or utility rebate, the room-by-room version of the workflow is what inspectors and program administrators expect to see documented.

System sizing FAQ

Quick answers to common HVAC sizing questions.

More tools

Explore the other HVAC calculators

Every calculator shares the same Manual J methodology, so your numbers stay consistent across tools. Pick the one that matches the answer you need.