CFM Calculator: Ton to CFM & CFM to Tons
Convert tons to CFM and CFM to tons at 350 or 400 CFM per ton, or estimate airflow from room volume and sensible load. Airflow assumptions do not measure actual refrigeration capacity.
Tons to CFM chart
Multiply tons by the selected airflow rate. These supply-air estimates help plan blower and duct capacity; they are not outdoor-air requirements or proof of delivered cooling.
| Cooling tons | At 350 CFM/ton | At 400 CFM/ton |
|---|---|---|
| 0.5 | 175 CFM | 200 CFM |
| 1 | 350 CFM | 400 CFM |
| 1.5 | 525 CFM | 600 CFM |
| 2 | 700 CFM | 800 CFM |
| 2.5 | 875 CFM | 1,000 CFM |
| 3 | 1,050 CFM | 1,200 CFM |
| 3.5 | 1,225 CFM | 1,400 CFM |
| 4 | 1,400 CFM | 1,600 CFM |
| 5 | 1,750 CFM | 2,000 CFM |
| 7.5 | 2,625 CFM | 3,000 CFM |
| 10 | 3,500 CFM | 4,000 CFM |
| 15 | 5,250 CFM | 6,000 CFM |
| 20 | 7,000 CFM | 8,000 CFM |
3 tons × 400 = 1,200 CFM; 3 tons × 350 = 1,050 CFM.
For example, 1,200 CFM / 400 = 3 tons. This reverses the airflow assumption; it does not measure cooling capacity.
Tonnage-driven airflow at 400 CFM per ton
Pick a tonnage to see the 400-CFM/ton supply-air reference scale linearly and watch the airflow animation change with it. The presets compare total system airflow as air moves from the air handler through the duct toward the conditioned space. Typical design rates are about 350–400 CFM/ton, with the approved setting determined by the matched system, operating mode, and climate. Use the main calculator to compare airflow settings and convert between CFM and tons, including the effect of lower airflow for humidity control.
Typical design airflow is about 350–400 CFM/ton. The approved rate depends on the matched system, operating mode, and climate; lower airflow improves dehumidification. This example uses 400 CFM/ton, and dot density scales with CFM.
Three ways to calculate required CFM
Use 350 only when approved for the matched equipment and operating mode.
Volume in cu ft, ACH = air changes per hour.
ΔT typically 20°F; 1.08 is the air constant.
Illustrative circulation ACH by space type
| Space | Illustrative ACH | Use and limitation |
|---|---|---|
| Bedroom | 5 | Site circulation preset; not outdoor-air minimum |
| Living room | 6 | Site circulation preset |
| Kitchen | 8 | Does not size cooking exhaust or makeup air |
| Bathroom | 8 | Does not replace exhaust-fan requirements |
| Office | 6 | Outdoor air depends on occupancy and use |
| Garage | 6 | Illustration only; do not return garage air to living space |
| Restaurant dining | 12 | Site preset; design outdoor air separately |
| Restaurant kitchen | Project-specific | Use hood capture, exhaust and makeup-air design |
| Hospital surgery | Project-specific | Use applicable healthcare ventilation criteria |
Common CFM sizing mistakes
- Sizing whole-house CFM but not per-room — leads to under-served rooms
- Ignoring duct losses — 15–25% of air is lost in unsealed ducts; design for delivered CFM
- Using 1 CFM per sq ft without a load check — a fixed area ratio cannot represent rooms with different glazing, occupancy or supply temperatures
- Mismatched blower speed and tonnage — running a 3-ton blower at 1,600 CFM (4 ton speed) destroys efficiency
- Undersized return air paths — supply CFM is meaningless if return can't match it
Why airflow, not just tonnage, decides delivered capacity
A cooling coil and compressor need the correct airflow to deliver their published performance. The blower's actual volume affects total capacity, sensible heat ratio and coil temperature, and it is sensitive to the resistance of filters, coils, ducts and terminals. ACCA Manual S uses the building loads and manufacturer performance at the proposed airflow and design conditions. A nominal 3-ton label does not tell you whether the installed system meets its sensible or latent load. Check the proposed flow before selecting equipment, then measure it after installation. A high thermostat temperature or persistent humidity problem may involve airflow, refrigerant operation or building load; airflow alone cannot diagnose the cause.
The 400-CFM/ton rule is a common planning reference, not a unit conversion like 12,000 BTU/h per ton. Reducing flow within an approved range can lower coil temperature and change moisture removal, which is why 350 CFM/ton may suit some humid-climate designs. Variable-speed and staged systems have manufacturer-defined airflow profiles, and high efficiency does not mandate a particular CFM/ton. The lower-flow setting must still satisfy sensible capacity and operating limits. Ask for the airflow used in the selection calculation, its associated sensible and latent capacities, and the blower setting that will provide it at the measured system resistance.
Reconciling the three CFM methods and balancing per room
The methods answer related but distinct questions. Tonnage × CFM/ton gives a whole-system airflow reference. Volume × ACH / 60 converts a selected circulation, outdoor-air or exhaust rate into CFM; the source of that ACH and the air path must be stated. Residential outdoor-air ventilation and commercial ventilation use separate requirements and cannot be satisfied simply by recirculating supply air. The sensible-load equation gives heat-transfer airflow for a specified room-to-supply temperature difference. Its 1.08 coefficient represents 60 minutes per hour × air density × specific heat at standard conditions, so elevation and air conditions can change it. Enter sensible load only, excluding the latent moisture load.
Room airflow needs to be reconciled with the selected equipment's design flow rather than assigning every room the same CFM per square foot. Use the room loads and supply temperature, then account for duct heat gains, leakage and the load-calculation method when comparing room sums with block and equipment loads. Room-by-room peaks can occur at different times, so their summed peaks are not automatically identical to the coincident whole-house peak. Return paths, transfer grilles or jumper ducts must accommodate supply flow when doors are closed. Restricted return paths can alter room pressure and increase infiltration. Commissioning should verify both total blower flow and distribution at the terminals under the intended operating conditions.
- Confirm airflow in manufacturer expanded performance data and blower tables; use AHRI information to identify the certified match
- Keep supply and return balanced — pressure imbalance wastes the airflow you sized
- Hold duct velocity (FPM) in a reasonable band so registers stay quiet
- Re-run the sensible-load method per room, then verify the rooms sum to the total
From CFM target to duct geometry, velocity, and equipment match
Once a CFM target exists for each run, the next step is turning that volume into duct dimensions, which is the domain of ACCA Manual D. Duct size follows from the required CFM and an acceptable air velocity in feet per minute (FPM): supply trunks commonly run around 700–900 FPM, with lower branch targets where needed for noise control. These are planning ranges; flex needs product-specific resistance data. Push velocity too high and registers can whistle and static pressure climbs; run it too low and ducts become oversized and expensive. You can translate the airflow figures from this page into trunk and branch dimensions with the duct size calculator, and the step-by-step method is walked through in how to size ductwork.
Airflow and capacity are a closed loop: the load sets the tonnage, the tonnage and the manufacturer's CFM/ton set the airflow, and the airflow sets the duct. If you have not yet established the cooling and heating load, start with the system size calculator and work back to this page. A constant-airflow ECM blower can hold its target over a limited pressure range, often using more power as resistance rises; other ECM control types behave differently. No motor removes the need for correctly sized ducts. Efficiency ratings such as SEER2, EER2, and HSPF2 describe tested equipment performance; they do not guarantee performance with restrictive or leaking installed ducts. Compare measured flow and external static pressure with the manufacturer tables before adjusting the blower. Then check register delivery and room comfort in the operating modes the household will actually use.
CFM to tons: divide by the airflow rate
1,400 CFM / 400 = 3.5 tons; 1,400 CFM / 350 = 4 tons.
Choose the rate used by your equipment design. Supply airflow alone cannot tell you the actual refrigeration capacity: entering-air humidity, indoor and outdoor temperatures, and the matched coil affect performance. Use manufacturer expanded performance data for equipment selection and a simplified Manual S check.
Airflow from room volume or sensible heat
20 * 15 * 8 ft = 2,400 cubic ft; at an illustrative 6 ACH, airflow is 240 CFM.
20,000 BTU/h / (1.08 * 20 degrees F) approximately 926 CFM. The 1.08 coefficient assumes standard-density air; altitude changes it.
At 1,200 CFM and 20°F, sensible heat transfer is 25,920 BTU/h. Do not compare this sensible-only result directly with a total cooling load that includes moisture.
The sensible equation addresses temperature change, not moisture removal. ACH presets do not replace an outdoor-air design. ASHRAE Handbook - Fundamentals explains air heat transfer; ACCA Manual D addresses residential duct design. Use the duct size calculator after estimating airflow, and confirm blower delivery against the manufacturer's static-pressure data.
Worked examples with the default inputs
The tonnage tab starts at 3 tons and 400 CFM/ton: 3 × 400 = 1,200 CFM. Switch only the rate to 350 and the result becomes 1,050 CFM. The reverse tab starts at 1,200 CFM: it represents 3 airflow-equivalent tons at 400, or approximately 3.43 at 350. Neither reverse answer is a measurement of refrigeration output.
The ACH tab starts with a 20 × 15 × 8-ft living room: volume is 2,400 cubic ft and the illustrative 6-ACH preset gives 2,400 × 6 / 60 = 240 CFM. The sensible-load tab starts at 20,000 BTU/h and 20°F: 20,000 / (1.08 × 20) = 925.93, displayed as 926 CFM. These defaults describe different tasks, so their results are not supposed to match.
| Sensible load | Room-to-supply ΔT | Calculated CFM |
|---|---|---|
| 2,160 BTU/h | 20°F | 100 |
| 4,320 BTU/h | 20°F | 200 |
| 20,000 BTU/h | 18°F | 1,029 |
| 20,000 BTU/h | 20°F | 926 |
| 20,000 BTU/h | 22°F | 842 |
Changing ΔT in the equation shows sensitivity, not an instruction to reduce blower flow until a target number appears. The coil must operate inside its approved range and deliver the required total and latent capacity. Use the room-by-room load estimate to organize room demands, then reconcile them with equipment performance.
References and assumptions
The 350 and 400 CFM/ton rates and room ACH presets are planning assumptions. They do not set outdoor-air requirements, establish an equipment minimum, or replace manufacturer commissioning instructions. The sensible equation assumes standard air; it excludes moisture heat transfer.
ACCA Manual S addresses equipment selection using loads and manufacturer performance. ASHRAE Handbook: duct design explains airflow resistance and sizing methods. Use the duct size calculator for a straight-duct screening check and a full Manual D design for the distribution system.
CFM FAQ
Quick answers to common HVAC sizing questions.
Explore the other HVAC calculators
Every calculator shares the same Manual J methodology, so your numbers stay consistent across tools. Pick the one that matches the answer you need.
BTU Calculator
Cooling or heating BTU/h for a room or whole home, adjusted for climate, insulation, sun exposure and occupancy.Open calculatorTonnage Calculator
Convert cooling load (BTU/hr) or square footage to AC tonnage and recommended unit size.Open calculatorHeating Load Calculator
Winter heat loss in BTU/h from design temperatures, insulation levels and natural air leakage.Open calculatorManual J Calculator
Simplified Manual J-style room-by-room estimate of heating, cooling and airflow. A free screening tool, not a full ACCA Manual J report.Open calculatorHVAC Sizing Calculator
End-to-end HVAC sizing: cooling load, heating load, nominal tons, CFM and trunk duct size in one flow.Open calculatorDuct Size Calculator
Round and rectangular duct dimensions for a target CFM, checked against friction rate and air velocity.Open calculator
Built and maintained by Danish Javaid · How this calculator works: Methodology · Editorial policy