Calculate HVAC Load

Window AC BTU Calculator

Find the window or room air conditioner size you need in BTU/hr from the room area, sun exposure, and occupancy — based on DOE room AC guidance.

Inputs
sq ft

Floor area of the single room the unit will serve.

Sunny rooms add 10%; heavily shaded rooms subtract 10%.

people

Add 600 BTU/hr for each person over two who regularly use the room.

Kitchens add 4,000 BTU/hr for cooking heat.

Results
Recommended window AC
5,000BTU/hr
Estimated room load
5,000BTU/hr

Formula

How window AC sizing works

Window and room air conditioners are sized on floor area, not on a full heat-load calculation. The U.S. Department of Energy's rule of thumb is 20 BTU/hr per square foot of conditioned floor space, with a handful of adjustments for the things that change a single room's load the most.

Base capacity
BTU/hr = Room area (sq ft) × 20
Adjusted capacity
BTU/hr = Base × Sun factor + 600 × (occupants − 2) + 4,000 (if kitchen)

Sun factor is 1.10 for a sunny room, 0.90 for a heavily shaded room, otherwise 1.00. Occupant and kitchen terms are only added when they apply.

The final number is rounded up to the nearest unit actually sold, so you never under-size. For a full room-by-room heat load or central system, use the more detailed BTU calculator or the AC size calculator instead of the area-based room-AC shortcut.

Reference

Window AC size by room area

The table below applies the DOE guidance to common room sizes with an average envelope and average sun. Bump up one size for very sunny rooms or busy kitchens.

Room areaBase load (BTU/hr)Recommended unitTypical room
100–150 sq ft2,000–3,0005,000 BTU/hrSmall bedroom, office
150–250 sq ft3,000–5,0006,000 BTU/hrBedroom, den
250–350 sq ft5,000–7,0008,000 BTU/hrLarge bedroom, studio
350–450 sq ft7,000–9,00010,000 BTU/hrLiving room
450–550 sq ft9,000–11,00012,000 BTU/hrOpen living/dining
550–700 sq ft11,000–14,00014,000 BTU/hrGreat room
700–1,000 sq ft14,000–20,00018,000 BTU/hrSmall open floor
1,000–1,500 sq ft20,000–30,00025,000 BTU/hrLarge open area (230V)

Pitfalls

Common window AC sizing mistakes

  • Buying the biggest unit that fits the window — oversizing causes short-cycling, a clammy room, and poor dehumidification.
  • Ignoring sun exposure — a west-facing room with afternoon sun needs about 10% more capacity than its floor area suggests.
  • Forgetting kitchen heat — cooking, the range, and the refrigerator add roughly 4,000 BTU/hr that area alone misses.
  • Not counting extra occupants — each person beyond two adds about 600 BTU/hr of sensible and latent load.
  • Trying to cool several rooms with one unit — air won't circulate around corners; size each room separately or use central cooling.
  • Overlooking electrical limits — units above about 15,000 BTU/hr usually need a dedicated 230-volt circuit.

Background

Why the right size matters more than the biggest size

A window air conditioner has two jobs: it lowers the temperature of the room (sensible cooling) and it wrings moisture out of the air (latent cooling). Both happen at the cold evaporator coil. The coil only pulls water vapor out of the air while it runs long enough for the coil surface to drop below the room's dew point and stay there. That is exactly the run time an oversized unit never gets. A 14,000 BTU/hr unit dropped into a 200 sq ft bedroom blasts the air down to the thermostat setpoint in a few minutes, satisfies the control, and shuts off before the coil has condensed much water. You end up with a room that reads 72°F on the thermostat but feels cold, damp, and clammy because the relative humidity is still high.

That start-stop pattern is called short-cycling, and it is the single most common consequence of buying capacity by the window opening rather than by the load. Each compressor start draws a large inrush of current and adds wear; frequent cycling shortens compressor life, raises energy use, and produces noticeable temperature swings. A unit sized close to the actual load runs in longer, steadier cycles, holds a more even temperature, and keeps the coil cold long enough to manage humidity. This is why the U.S. Department of Energy's room air conditioner sizing guidance, and the rounding logic in this tool, aim for the smallest standard unit that comfortably meets the calculated load rather than the largest one that physically fits.

Single-room cooling is also a fundamentally different problem from whole-house cooling. A window or room unit conditions the air in the space it is mounted in; it has no ductwork to push cold air around corners, down hallways, or through closed doors. If you need to cool several connected rooms or an entire home, the answer is not a bigger window unit but a properly sized ducted system. For that, run a room-by-room load with the BTU calculator or compare whole- home capacity with the AC size calculator, which translate the load into tons (one ton equals 12,000 BTU/hr) the way central equipment is rated.

Buyer's guide

Efficiency, ratings, and electrical fit

Once you know the BTU/hr you need, the next decision is efficiency. Room air conditioners are rated by their Combined Energy Efficiency Ratio (CEER), which the DOE adopted to replace the older EER figure. CEER accounts for standby and off-cycle power, not just cooling efficiency while running, so it is a fairer comparison between models of the same capacity. A higher CEER means the same cooling for fewer watts. ENERGY STAR certified room units, administered by the EPA, carry a CEER meaningfully above the federal minimum and are a good shortcut to a low-running-cost model when you are comparing two units with the same BTU/hr rating.

Electrical fit is the constraint people most often overlook. Standard household receptacles in North America deliver 115V, and most window units up to roughly 12,000 BTU/hr are designed to plug into an ordinary 115V circuit. As capacity climbs, the running current rises with it: units in the 14,000 to 25,000 BTU/hr range frequently require a dedicated 230V circuit and a matching outlet, which means an electrician and a new line, not just a different plug. Check the nameplate voltage and amperage before you buy, and confirm the circuit is not already shared with other large loads. The standard sizes below show where the voltage transition typically lands.

  • 5,000–6,000 BTU/hr — small bedrooms and offices; 115V, plugs into a standard outlet.
  • 8,000–12,000 BTU/hr — bedrooms and living rooms; still usually 115V but may want a dedicated circuit.
  • 14,000–18,000 BTU/hr — large or sunny rooms; often 230V with a non-standard outlet.
  • 25,000 BTU/hr — large open areas; 230V dedicated circuit and professional install.

Finally, remember that the load drivers built into this calculator — heavy direct sun (about a 10% increase), extra occupants (about 600 BTU/hr each beyond two), and kitchen heat (about 4,000 BTU/hr for the range and refrigerator) — change the answer more than picking a fancier model does. Size for the real room first using DOE guidance, confirm the circuit can carry it, then choose the highest-CEER ENERGY STAR unit in that capacity. That order gives you a room that is both genuinely comfortable and inexpensive to run.

Window AC sizing FAQ

Quick answers to common HVAC sizing questions.

More tools

Explore the other HVAC calculators

Every calculator shares the same Manual J methodology, so your numbers stay consistent across tools. Pick the one that matches the answer you need.