Calculate HVAC Load

HVAC Unit Converter

Convert HVAC capacity units instantly — between BTU/hr, tons of refrigeration, kilowatts, kcal/hr, and airflow (CFM).

Inputs

The value is converted to BTU/hr first, then to every other unit.

Results
BTU per hour
36,000BTU/hr
Tons of refrigeration
3tons
Kilowatts
10.551kW
Kilocalories per hour
9,078kcal/hr
Equivalent airflow
1,200CFM

Formula

The conversion math

Every conversion routes through BTU/hr as the common base unit. The input is first converted to BTU/hr, then divided out to each target unit. Airflow is derived from tonnage at the residential standard of 400 CFM per ton — the same factor used in our CFM calculator. If you are sizing a system rather than converting a known capacity, start from the tonnage calculator instead.

Tons
Tons = BTU/hr ÷ 12,000

1 ton of refrigeration = 12,000 BTU/hr.

Kilowatts
kW = BTU/hr ÷ 3,412.142

1 kW = 3,412.142 BTU/hr (thermal).

Kilocalories
kcal/hr = BTU/hr ÷ 3.965667

1 kcal/hr = 3.965667 BTU/hr.

Airflow
CFM = Tons × 400

Residential standard; 350 CFM/ton for high-efficiency.

Reference

Common HVAC capacity equivalents

BTU/hrTonskWkcal/hrCFM (at 400/ton)
6,0000.51.761,513200
9,0000.752.642,270300
12,0001.03.523,026400
18,0001.55.284,539600
24,0002.07.036,052800
36,0003.010.559,0781,200
48,0004.014.0712,1041,600
60,0005.017.5915,1302,000

Pitfalls

Common conversion and sizing mistakes

  • Confusing thermal kW (capacity) with electrical kW (power draw) — they differ by the system's COP/EER and are never equal
  • Using 3,517 W/ton interchangeably with the converter's kW value — that figure is rounded; the exact divisor is 3,412.142 BTU/hr per kW
  • Mixing kcal/hr and kW from different region spec sheets without converting both to a common base first
  • Treating the CFM result as a final duct design — it is a 400 CFM/ton reference, not a Manual D airflow calculation
  • Rounding tonnage during conversion — keep exact values for math, and only round to half-ton increments when selecting actual equipment
  • Assuming a heating BTU rating converts the same way — combustion equipment also has an efficiency (AFUE) that input vs. output ratings must account for

Background

Why HVAC capacity wears so many different units

The cooling and heating world inherited its vocabulary from several centuries of engineering, and the units never converged on a single standard. In the United States the British thermal unit per hour (BTU/hr) remains the working currency: it is the rate of heat that raises one pound of water one degree Fahrenheit, accumulated over an hour. Equipment nameplates, AHRI certified ratings, and ACCA Manual J load reports all speak in BTU/hr, which is why this converter routes every input through it as the common base.

The "ton" is the most quietly historical unit on the dial. It does not measure weight — it measures the cooling effect of melting one short ton (2,000 lb) of ice over 24 hours. The latent heat of fusion of ice is about 144 BTU per pound, so 2,000 lb × 144 BTU ÷ 24 hours lands on the familiar 12,000 BTU/hr that defines one ton of refrigeration. That ice-house heritage is why a residential split system is sold as a 2-, 3-, or 5-ton unit rather than by a metric figure, and why tonnage maps cleanly onto the airflow rule of roughly 400 CFM per ton used throughout this site.

The kilowatt is the unit the rest of the world reaches for. Because 1 kW equals 3,412.142 BTU/hr, a nominal 1-ton system is about 3.517 kW of thermal capacity. The kilocalorie per hour persists on spec sheets across parts of Europe, the Middle East, and Asia, where 1 kcal/hr equals 3.965667 BTU/hr — so a 12,000 BTU/hr machine is listed as roughly 3,026 kcal/hr. Knowing which dialect a given catalog uses is half the battle when comparing imported and domestic equipment.

In practice

Reading the unit on a real spec sheet

The single most consequential distinction this tool cannot make for you is whether a kilowatt figure describes thermal capacity or electrical input. A heat pump rated at 10.5 kW of cooling does not draw 10.5 kW from the panel; it might draw 3 kW and move the rest by relocating heat, and that leverage is its coefficient of performance. US efficiency ratings — SEER2, EER2, HSPF2 for heat pumps, and AFUE for combustion furnaces — all encode that same input-versus-output relationship in different ways. When a European data sheet lists both a capacity in kW and a power consumption in kW, treat only the capacity figure as something to convert here, and feed the rest into an efficiency comparison instead.

Combustion heating adds a second trap. A furnace may advertise an input rating and an output rating; the difference is its AFUE. Converting an 80,000 BTU/hr input furnace as though it delivered 80,000 BTU/hr overstates usable heat by 20 percent on an 80 percent AFUE unit. Always confirm whether a heating BTU number is gross input or net output before converting it to tons or kW.

  • US residential and light commercial: tons and BTU/hr dominate, anchored by AHRI ratings and ACCA Manual J/S
  • International and chiller markets: kW of thermal capacity, often alongside electrical kW input
  • Legacy and some regional catalogs: kcal/hr, especially older boiler and packaged-unit literature
  • Airflow context: CFM in the US, m³/h or L/s under SI conventions referenced in ASHRAE 62.1 and 62.2 ventilation rates

Standards

Where these conversions sit in the design workflow

Converting units is a clerical step, not a sizing decision. The numbers you convert should originate from a defensible load calculation — for homes, an ACCA Manual J heat-gain and heat-loss analysis that accounts for envelope U-values and R-values, infiltration, internal gains, and your IECC climate zone. The ASHRAE Handbook of Fundamentals supplies the underlying thermal property data, while ASHRAE 62.2 sets the residential ventilation rates that drive much of the outdoor airflow a system must condition. Only after that work is done does converting the result into tons, kW, or kcal/hr help you shop a catalog.

The 400 CFM per ton figure deserves the same caution. It is a planning shorthand, useful for sanity-checking a blower, but real duct design follows ACCA Manual D and may call for 350 CFM per ton in high-latent climates or higher-efficiency equipment. Once you have a converted tonnage you trust, walk it back through the tonnage calculator to confirm the size against your actual load, and use the CFM calculator for airflow that reflects your ducts rather than the rule of thumb. For a deeper tour of how these units relate to one another, the guide to heat load calculation units works through the same conversions with worked examples and the rationale behind each constant.

Treat this converter as the bilingual interpreter between a US tons-and-BTU world and an international kW-and-kcal world. It will tell you that 5 tons, 60,000 BTU/hr, 17.59 kW, and roughly 15,130 kcal/hr all describe the same machine — but it will not tell you whether that machine is the right one for your building. Pair the conversion with a proper Manual J load and a verified airflow plan, and the units stop being a source of confusion and become exactly what they should be: a precise, interchangeable description of the same physical capacity.

Unit Converter FAQ

Quick answers to common HVAC sizing questions.

More tools

Explore the other HVAC calculators

Every calculator shares the same Manual J methodology, so your numbers stay consistent across tools. Pick the one that matches the answer you need.