How to Size Ductwork: A Practical Guide

By Danish Javaid, founder & editor · Published · Updated

Tapered duct trunk and narrower branches delivering air to registers, with round and rectangular duct sections.

To size a duct, turn the room's sensible load into CFM, subtract the filter, coil and grille losses from the blower's rated static pressure, divide what is left by the longest run's effective length to get a friction rate, and read the duct diameter for that CFM at that rate. For a 200 CFM bedroom run at 0.08 in. w.c. per 100 ft the answer is an 8 inch round duct. This page does all five steps on one house so you can check each number; a licensed designer using ACCA Manual D has the final say on a real project.

The house: a 3-ton system and six rooms

Assume a Manual J report gives the sensible loads below and the Manual S selection moves 1,200 CFM (3 tons at 400 CFM per ton). Cooling airflow per room is its sensible load divided by 1.08 × the supply-to-room temperature difference; at 20°F that divisor is 21.6.

Room CFM = sensible load ÷ (1.08 × ΔT)

1.08 is for standard air near sea level. Use the ΔT the selected equipment actually delivers; at 18°F every room needs about 11% more air.

RoomSensible load (BTU/h)CFM at 20°FRound duct at 0.08 in./100 ft
Living room8,640400Two runs of 200 CFM, 8 in. each
Kitchen4,3202008 in.
Primary bedroom4,1041908 in.
Bedroom 23,2401508 in.
Bedroom 32,3761107 in.
Office3,2401508 in.
Total25,9201,200matches the equipment airflow
Loads are assumed. The room CFMs sum to the 1,200 CFM the equipment moves, which is the check to run before choosing any duct size. Heating airflow needs its own check.

Step 1: the pressure budget

Start from the blower table at 1,200 CFM and your speed setting; assume it rates the blower at 0.50 in. w.c. of external static pressure. Components that sit outside the rating boundary come out of that figure. Assume a filter of 0.10, an external coil of 0.20 and registers and grilles of 0.05. Do not subtract anything the rating already includes, and note that 0.50 is a common rating point, not a design requirement.

Available for ducts: 0.50 − 0.10 − 0.20 − 0.05 = 0.15 in. w.c.

Step 2: effective length of the longest path

Take the controlling supply run plus the matching return path. Every elbow, takeoff, boot and transition adds an equivalent length of straight duct, from Manual D's fitting tables. Assume the longest supply run is 55 ft of straight duct plus 65 ft of fittings, and the return path is 70 ft all in. Total effective length is 120 + 70 = 190 ft. A tight elbow or a badly made takeoff can cost more pressure than its physical length suggests, so the fittings are where this number is usually underestimated.

Step 3: the friction rate

Friction rate = available static pressure × 100 ÷ total effective length

Inches water column and feet give in. w.c. per 100 ft.

0.15 × 100 ÷ 190 = 0.079, which rounds to 0.08 in. w.c. per 100 ft for this house. A longer path or an extra 0.05 of component loss pushes that rate lower and every duct larger, which is why a duct size is only meaningful alongside its budget.

Step 4: read the duct size

Round duct capacity at a fixed friction rate comes from the Darcy-Weisbach relation. The values below use the same smooth-metal-duct equation as our duct size calculator, so treat them as a check against Manual D's friction chart, not a replacement for it. Flex duct and heavily lined duct lose more pressure at the same size.

Round duct (in.)CFM at 0.08 in./100 ftVelocity (ft/min)
560442
699502
7149559
8214613
10389713
12633806
14954893
Smooth galvanized round duct, standard air. Compare the airflow needed with the capacity in the row, then round up to the next stock size.

That is how the table above gave 8 inches for 200 CFM: a 7 inch duct tops out at 149 CFM. Bedroom 2 at 150 CFM just misses 7 inches (149), so it takes an 8. Trunks step down as branches peel off. Taking the living room first, the trunk after each takeoff carries less air:

Trunk sectionCFM carriedRound duct at 0.08Velocity
Leaving the air handler1,20016 in.859
After the living-room takeoffs80014 in.748
After the kitchen60012 in.764
After the primary bedroom41012 in.522
Last section to Bedroom 3 and office2609 in.589
Sections are sized for the CFM that remains downstream. A rectangular trunk uses the equivalent round diameter from Manual D, and the trunk can be reduced in size only as far as space and noise allow.

Velocity is a noise and wasted-material check, not a substitute for the friction rate. Take its limits from Manual D and the register manufacturer's data. Returns follow the same budget as supplies: two returns carrying 600 CFM each would be 12 inch round at this rate, and a closed bedroom door needs a pathway such as a transfer grille or jump duct so the supply does not pressurize the room.

When an existing run is too small

Say a bedroom needs 150 CFM and the installed branch is 5 inch round. The friction model gives about 0.42 in. w.c. per 100 ft, roughly five times the 0.08 design rate, with air moving at 1,100 ft/min. The room will be noisy and starved, and the fix is a larger branch (8 inch here) or a second run. A bigger blower pushes the duct harder rather than fixing it, and raising total static pressure can reduce airflow across the coil, which is the subject of the static pressure guide.

Five ways a duct plan goes wrong

  • Sizing from tonnage alone. It gives every room the same duct regardless of load.
  • Ignoring fitting length. The real friction rate ends up well above the design value.
  • Subtracting a component twice. Check what the blower's rated pressure already includes.
  • Using the cooling ΔT for heating. Supply air is much hotter in heating, so heating CFM needs its own calculation.
  • Forgetting returns and balancing. Equal-friction sizing does not guarantee each room gets its designed airflow; commissioning measures it and balancing dampers fix it.

Use the CFM calculator for room airflow (it now also converts between CFM and tons), the static pressure calculator to tally component losses, and the J, S and D walkthrough to see how the load, equipment and duct steps hand off.

Sources: ACCA Manual D (residential duct design); ACCA Manual J; ACCA Manual S. The CFM equation uses the standard-air constant 1.08; friction values come from this site's duct model.

Calculation guidance is reviewed against our published methodology. To report an error or request a correction, use the contact page.

Written and maintained by Danish Javaid, founder & editor. About this site.

Revision history

  • : Rewrote as a single start-to-finish worked example and replaced the approximate duct-capacity table with values from the site's duct model.
  • : Added a worked check of an undersized 5-inch bedroom branch and a table of common duct-sizing mistakes.